Inspection Checklist (8 items)
✅ Before the Inspector Arrives(2) Verify all NEC labels installed ✓ [1] [2] All NEC-required labels and placards must be installed at main panel, disconnects, inverter, and conduit runs before inspection.
Verify fire access pathways ✓ [3] [4] Confirm solar array installation meets fire department access pathway requirements. Inspector will verify setbacks from ridge, hips, and valleys.
🔍 Day-of Inspection(4) Confirm equipment matches plans ✓ [5] [6] Installed equipment (modules, inverter, racking) must match the approved plans. Serial numbers and models should be verifiable.
Test rapid shutdown system ~ [7] [8] Inspector may test the rapid shutdown system to verify it functions correctly per NEC 690.12.
Verify grounding and bonding ✓ [9] [10] Inspector will verify equipment grounding conductors, grounding electrode conductors, and module/racking bonding.
Have approved plans on site ✓ [15] A copy of the approved permit plans must be available on site during inspection. Digital copies on a tablet are typically acceptable.
⚠️ Common Failure Points(2) ! Missing or incorrect NEC labels ✓ [11] [12] Most common fail reason: labels missing, placed incorrectly, or with wrong content. Double-check all label locations against NEC 690.56 before inspection.
! Exposed or improperly secured wiring is a common fail. Ensure all conductors are properly routed, supported, and protected.
Inspection requirements may vary by project. Always confirm specific inspection criteria with your inspector or local AHJ.